connect to
BTS port
Battery or Battery
Enclosure
(2)(a)
(2)(b)
(1)
Route the DC cables from the battery bank to the inverter/charger.
(2) Install a DC fuse (a) and DC disconnect switch (b) or a DC circuit breaker (c) between the inverter/charger and
the battery on the positive cable.
(3) Open and lockout the DC disconnect switch or DC circuit breaker.
(4) Connect one connector on the POSITIVE (+) cable to the BATTERY POSITIVE terminal on the inverter/charger.
Connect in the order shown on Terminal Connection below. If the bolt has a nut and washer, remove them first.
(5) Connect the other connector to the POSITIVE (+) terminal on the battery.
(6) Connect one connector on the NEGATIVE (–) cable to the BATTERY NEGATIVE terminal on the inverter/charger.
Connect in the order shown on Terminal Connection below. If the bolt has a nut and washer, remove them first.
(7) Connect the other end of the cable to the NEGATIVE (–) terminal on the battery.
(8) Attach the DC terminal covers to the inverter/charger
using the screws provided.
(2)(c)
(4)
(3)
(5)
(6)
(7)
(8)
Nut
Washer
Connector
Battery Terminal on
the inverter
Terminal Connection