Installation
1–14 975-0637-01-01 Rev B
This guide for use by qualified personnel only
DC Disconnects
and Overcurrent
Devices
The DC circuit from the battery to the inverter/charger must be equipped with a
disconnect and overcurrent protection device. Refer to your applicable
installation code.
Type This device usually consists of a circuit breaker, a “fused-disconnect,” or
a separate fuse (installed at each positive cable near the battery terminal) and
DC disconnect. Do not confuse AC circuit breakers with DC circuit breakers.
They are not interchangeable.
Rating The rating of the fuse or breaker must be matched to the size of cables
used in accordance with the applicable installation codes.
Location The breaker or fuse and disconnect should be located as close as
possible to the battery in the positive cable. Applicable codes may limit how far
the protection can be from the battery.
Table 1 -2 Recommended Battery Cable
a
Sizes
a.70°C thermoplastic insulated cable
Model Maximum
Current (A)
Cable Length
< 1.5 m
Cable Length
1.5 to 3.0 m
Conduit / (Free Air)
SW 2524 230 120
50 mm
2
(25 mm
2
)70 mm
2
(35 mm
2
)
SW 4024 230 200
240 mm
2
(120 mm
2
) 300 mm
2
(150 mm
2
)
IMPORTANT: Using a smaller gauge cable or a longer cable may cause the
inverter to shut down under heavy load.
WARNING
FIRE AND BURN HAZARD
Do not use battery cables that are insufficiently sized for expected current.
Check local electrical codes carefully.
Failure to follow this instruction can result in death or serious injury.
Table 1 -3 Recommended Fuse and Breaker Sizes
Model Fuse Size (A) Minimum Breaker Size (A)
SW 2524 230 250 250
SW 4024 230 250 250
ConextSWEUROInstallationGuide.book Page 14 Wednesday, December 5, 2012 10:55 AM