Redline
D.30
Comfort functions
A
B
C
D
E
F
G
X
Function
Measurement, visualisation and
logging of voltage, current,
frequency, hours of operation,
power, energy, cos ϕ , etc.
Standards
EN 61010-1, BS EN 60051-1-2
Series MT
Applications
Measurement of all possible electrical values from simple measurement as
voltage, current, frequency over more complex such as power and energy,
to all-in-one measurement with the netanalysing devices. To avoid
down-time due to abnormal situations, i.e. power-supply voltage too high,
absorbed power too high, etc., leading to malfunctionning and even break-
down of the machinery, the measurement and monitoring of the electrical
values like voltage, current, power, energy etc. is an absolute must and even
an indespensable asset when it comes to preventive maintenance.
Features
AC measurement devices with analogue as well as with digital technology and
readout are available. The simple devices (one measurement only i.e. voltage,
current, frequency) are only available in single phase, while the complex
devices (more than one measurement i.e. power, energy, net analyser) are also
available in 3-phase execution. High currents can be measured through the
intermediate use of a current transformer (for the analogue amp-meter
combined with an interchangeable scale-plate). All devices have very good
precision and have also a very low self-consumption to limit as much as
possible the measurement error. Using one monophase-volt or amp-meter in a
3-phase system is possible by using the appropriate selector switch.
The energy meters as well as the net analysers are true RMS measuring devic-
es. Monitoring and logging all electrical values on to a PC is possible by using
the MT PRG software.
More technical data
Dimensions
website
pg D.48
Measurement Instruments
Performance
Readout
Scale selection
Own consumption current meters
Own consumption other meters
Operating temperature range
Test voltage
Class of precision (accuracy)
Overload current coils
- 1 second
- Continuous
Overload voltage coils
- 0.5 second
- Continuous
Vibration resistance
Shock resistance
Protection degree
Screws
Terminal capacity: min
max
Analogue instruments
Polycarbonate+carbon needle
Interchangeable
scaleplate
0.3VA
1.5VA
-10 ... +55ºC
2000V at 50Hz during 1 minute
1.5
(0.5 for frequency meter)
10xIn
2xIn
2xUn
1.2xUn
0.35 mm at 10/55Hz on 3 axes,
duration of 6 hours
50g
IP40
Pozidriv 1
1x1 mm
2
1x16 mm
2
or 2x6 mm
2
Digital instruments
3digit 7segment LED
Dip-switches
1.5VA
1.5VA
-5 ... +55ºC
2000V at 50Hz during 1 minute
0.5%
±1 digit referred to full scale
10xIn
2xIn
2xUn
1.2xUn
0.35 mm at 10/55Hz on 3 axes,
duration of 6 hours
50g
IP40
Pozidriv 1
1x1 mm
2
1x16 mm
2
or 2x6 mm
2
Net analyser
LCD display
Dip-switches
-
-
-10 ... +55ºC
2000V at 50Hz during 1 minute
0.5%
±1 digit referred to full scale
10xIn
2xIn
2xUn
1.2xUn
0.35 mm at 10/55Hz on 3 axes,
duration of 6 hours
50g
IP40
Pozidriv 1
1x1 mm
2
1x16 mm
2
or 2x6 mm
2
Komentarze do niniejszej Instrukcji